    Input Module(J-EI6031)
    Product Overview:

    (1)Dual input; receives alarm signals from passive normally-on/off monitors such as pressure switch, water flow indicator, flammable gas detector, independent detector for electric fire protection, as well as operating signals from linkage equipment such as 280°C fire-resisting damper. Both inputs have the “operating” indicators directly indicate the statuses of alarming/operating.

      (2)  A protective circuit is added to the signal detection area to avoid incorrect wiring or damage of the module caused by short circuit. As for equipment that provides passive normally-on alarm signals, the input module may detect the shut-off failure of its attached equipment when load resistance is connected in the contact spots, ensuring system stability and reliability.




    . Electronically encoded with only one ID; online addressing by controller or addressing by encoder; automatic log-in, convenient installation and debugging.

    · A CPU and smart software are built in, high smartness level.

    · Convenient wiring, good-looking appearance, suitable to DH86 junction box.

     

     


     · Working temperature:-10℃ ~+50℃

     · Bus working voltage: 24V Pulsating voltage

     · Standby current:<0.35mA

     · Operating current:<0.8mA

    · Alarm indicating lamp: Red, flickers during routing inspection, keeps lighting during alarming

    · Carried standard:GB16806-2006 Fire-Fighting Linkage Control System

    · Working humidity: <95% RH (No condensation of moisture)

    · Wiring system: Two-wire bus (non-polarized)

    · Bus length: ≤2000m

    · Load resistance: 1/4W  47kW

    · Protection level of casing: IP30